D-120 Parameter Reference
AC30 series Variable Speed Drive
PMAC SVC
Parameters::Motor Control::PMAC SVC
Only available if PMAC MOTOR selected in Control Mode.
Parameters related to the SVC Control mode of a PMAC Motor
Parameter Name
No.
Path
Default
Range
Units
Writable
PMAC SVC Auto Values
0467
Parameters::Motor Control::PMAC SVC
TRUE
ALWAYS
Selection of pre-calculated values
When selected, do some pre-calculations of the following PMAC SVC parameters:
PMAC SVC LPF Speed Hz
PMAC SVC P Gain
PMAC SVC I Gain Hz
PMAC SVC LPF Speed Hz
0468
Parameters::Motor Control::PMAC SVC
60.00
0.00 to 10000.00
Hz
ALWAYS
Set the Low Pass Filter frequency of the estimated speed.
PMAC SVC P Gain
0469
Parameters::Motor Control::PMAC SVC
1.00
0.00 to 10000.00
ALWAYS
Set the Proportional gain of the PI corrector used for extracting speed and position.
PMAC SVC I Gain Hz
0470
Parameters::Motor Control::PMAC SVC
20.00
0.00 to 10000.00
Hz
ALWAYS
Set the Integral frequency of the PI corrector used for extracting speed and position.
PMAC SVC Open Loop
Strt
0476
Parameters::Motor Control::PMAC SVC
TRUE
ALWAYS
This parameter is used to enable/disable a specific startup procedure when the motor/drive is switched ON (starting rotation). This
parameter is also used to work in up down motion, where we need to go down to zero speed or crossing the zero speed point.