D-222 Parameter Reference
AC30 series Variable Speed Drive
PNO
Name
Path
Type
Default
Range
Units
WQ
View
Notes
MBus
1633
Application User Boost
Parameters::Motor Control::Fluxing VHz
REAL
0.00
0.00 to 25.00
%
ALWAYS
OPERATOR
03793
1634
Start Delay
Parameters::Motor Control::Motor Sequencer
TIME
0.000
0.000 to 30.000
s
STOPPED
TECHNICIAN
03795
1635
Delay To Start
Parameters::Motor Control::Motor Sequencer
TIME
0.000 to Max
s
NEVER
TECHNICIAN
03797
1636
Manufacturing Flags
Parameters::Device Manager::Drive info
WORD
NEVER
ENGINEER
03799
1637
Engineer Password
Parameters::Keypad::Graphical Keypad
WORD
0000
ALWAYS
TECHNICIAN
03801
1640
Modbus Password
Setup::Communications::Option
Parameters::Option Comms::Modbus RTU
WORD
0000
ALWAYS
TECHNICIAN
03807
1641
VDC Lim Enable
Parameters::Motor Control::DC Link Volts Limit
BOOL
FALSE
STOPPED
TECHNICIAN
03809
1642
VDC Lim Level
Parameters::Motor Control::DC Link Volts Limit
REAL
91.0
78.0 to 100.0
%
STOPPED
TECHNICIAN
03811
1643
VDC Lim Active
Parameters::Motor Control::DC Link Volts Limit
BOOL
NEVER
TECHNICIAN
03813
1644
VDC Lim Output
Parameters::Motor Control::DC Link Volts Limit
REAL
x.x
Min to Max
Hz
NEVER
ENGINEER
03815
1645
Pwrl Enable
Parameters::Motor Control::Power Loss Ride Thru
BOOL
FALSE
STOPPED
TECHNICIAN
03817
1646
Pwrl Trip Threshold
Parameters::Motor Control::Power Loss Ride Thru
REAL
52.0
20.0 to 60.0
%
STOPPED
TECHNICIAN
03819
1647
Pwrl Control Band
Parameters::Motor Control::Power Loss Ride Thru
REAL
2.0
0.0 to 20.0
%
STOPPED
TECHNICIAN
03821
1648
Pwrl Accel Rate
Parameters::Motor Control::Power Loss Ride Thru
REAL
100
1 to 500
Hz/s
STOPPED
TECHNICIAN
03823
1649
Pwrl Decel Rate
Parameters::Motor Control::Power Loss Ride Thru
REAL
100
1 to 500
Hz/s
STOPPED
TECHNICIAN
03825
1650
Pwrl Time Limit
Parameters::Motor Control::Power Loss Ride Thru
TIME
30.000
0.000 to 300.000
s
STOPPED
TECHNICIAN
03827
1651
Pwrl Active
Parameters::Motor Control::Power Loss Ride Thru
BOOL
NEVER
TECHNICIAN
03829
1658
Current Diff Level
Parameters::Trips::Current Sensor Trip
REAL
25.00
0.00 to 100.00
%
ALWAYS
OPERATOR
03843
1659
Modbus TCP Password
Setup::Communications::Base Modbus
Parameters::Base Comms::Modbus
WORD
0000
ALWAYS
TECHNICIAN
03845
1661
PTP Enable
Setup::Communications::PTP
Parameters::Base Comms::PTP
BOOL
FALSE
ALWAYS
TECHNICIAN
03849
1663
Encoder Supply
Setup::Inputs and Outputs::SB Encoder Slot1
Parameters::System Board::Encoder Slot 1
USINT
(enum)
0
0:5 V
1:12 V
2:15 V
3:20 V
STOPPED
TECHNICIAN
03853
1664
Encoder Lines
Same as PNO 1663
DINT
2048
1 to 100000
STOPPED
TECHNICIAN
03855
1665
Encoder Invert
Same as PNO 1663
BOOL
FALSE
STOPPED
TECHNICIAN
03857
1666
Encoder Type
Same as PNO 1663
USINT
(enum)
0
Same as PNO 1514
STOPPED
TECHNICIAN
03859
1667
High Input Threshold
Same as PNO 1663
BOOL
FALSE
STOPPED
TECHNICIAN
03861
1668
Encoder Speed
Parameters::System Board::Encoder Slot 1
REAL
x.
Min to Max
RPM
NEVER
TECHNICIAN
03863
1669
Encoder Count Reset
Same as PNO 1663
BOOL
FALSE
ALWAYS
TECHNICIAN
2
03865
1670
Encoder Count
Parameters::System Board::Encoder Slot 1
DINT
-214783648 to 214783647
NEVER
TECHNICIAN
03867
1671
Encoder Lines
Parameters::System Board::Encoder Slot 2
DINT
2048
1 to 100000
STOPPED
TECHNICIAN
03869
1672
Encoder Invert
Parameters::System Board::Encoder Slot 2
BOOL
FALSE
STOPPED
TECHNICIAN
03871
1673
Encoder Type
Parameters::System Board::Encoder Slot 2
USINT
(enum)
0
Same as PNO 1514
STOPPED
TECHNICIAN
03873
1674
High Input Threshold
Parameters::System Board::Encoder Slot 2
BOOL
FALSE
STOPPED
TECHNICIAN
03875
1675
Encoder Speed
Parameters::System Board::Encoder Slot 2
REAL
x.
Min to Max
RPM
NEVER
OPERATOR
03877
1676
Encoder Count Reset
Parameters::System Board::Encoder Slot 2
BOOL
FALSE
ALWAYS
TECHNICIAN
2
03879
1677
Encoder Count
Parameters::System Board::Encoder Slot 2
DINT
-214783648 to 214783647
NEVER
TECHNICIAN
03881
1678
Output Enable
Setup::Inputs and Outputs::System Board Option
Parameters::System Board::System Board IO
BOOL
FALSE
ALWAYS
ENGINEER
03883
1679
Output Source
Same as PNO 1678
USINT
(enum)
0
0:SYSTEM BOARD SLOT 1
1:SYSTEM BOARD SLOT 2
2:SYNTHETIC ENCDR
3:DIGITAL OUTPUTS
STOPPED
ENGINEER
03885
1680
Output Voltage
Same as PNO 1678
USINT
(enum)
0
Same as PNO 1663
ALWAYS
ENGINEER
03887
1681
PTP Log Sync Interval
Same as PNO 1661
SINT
-1
-1 to 0
ALWAYS
ENGINEER
03889
1682
Random Pattern AFE
Parameters::Motor Control::Pattern Generator
BOOL
FALSE
ALWAYS
ENGINEER
03891
1683
PTP Clock Mode
Same as PNO 1661
USINT
(enum)
0
0:E2E
ALWAYS
ENGINEER
03893
1684
PTP Clock Type
Same as PNO 1661
USINT
(enum)
0
0:MASTER OR SLAVE
1:SLAVE ONLY
ALWAYS
ENGINEER
03895
1685
PTP Lock Threshold
Same as PNO 1661
REAL
0.5
0.1 to 100.0
us
ALWAYS
ENGINEER
03897
1686
PTP Priority2
Same as PNO 1661
USINT
128
0 to 255
ALWAYS
ENGINEER
03899
1687
PTP Offset
Monitor::Communications::PTP
Parameters::Base Comms::PTP
DINT
Min to Max
ns
NEVER
OPERATOR
03901
1688
PTP Locked
Same as PNO 1687
BOOL
NEVER
OPERATOR
03903
1689
PTP State
Same as PNO 1687
USINT
(enum)
0:NONE
1:INITIALISNG
2:FAULTY
NEVER
OPERATOR
03905