2PREF Name Block Type Range Default ro\rw Notes
111.08 REFERENCE TYPE PHASE TUNING ENUM 0 : SQUARE
1 : SINUSOIDAL
2 : TRIANGULAR
SQUARE rw
111.09 SPEED AMPLITUDE PHASE TUNING REAL 0.0000 to 100.0000 rev/s 0.1000 rev/s rw
111.12 RUN TR FUNC
TEST
PHASE TUNING BOOL 0 : FALSE
1 : TRUE
FALSE rw
111.13 NO OF
MEASRMENTS
PHASE TUNING INT 1 to 10000 100 rw
111.14 TORQUE
AMPLITUDE
PHASE TUNING REAL 0.00 to 100.00 % 20.00 % rw
111.15 TRANSF FUNC
TYPE
PHASE TUNING ENUM 0 : SPEED TRANSFR
FN
1 : OPEN LP TRANS FN
2 : CURRENT LP TR FN
OPEN LP TRANS FN rw
111.16 POSN AMPLITUDE PHASE TUNING REAL 0.0000 to 100.0000 deg 1.0000 deg rw
111.17 MEASURMENTS
DONE
PHASE TUNING INT _ 0 ro Output
112.01 ENABLE POWER LOSS
CNTRL
BOOL 0 : FALSE
1 : TRUE
FALSE rw
112.02 TRIP THRESHOLD POWER LOSS
CNTRL
REAL 0 to 1000 V 447 V rw 3,5
112.03 CONTROL BAND POWER LOSS
CNTRL
REAL 0 to 1000 V 20 V rw
112.04 ACCEL TIME POWER LOSS
CNTRL
REAL 0.01 to 300.00 s 10.00 s rw
112.05 DECEL TIME POWER LOSS
CNTRL
REAL 0.01 to 300.00 s 5.00 s rw
112.06 TIME LIMIT POWER LOSS
CNTRL
REAL 0.00 to 300.00 s 30.00 s rw