EasyManua.ls Logo

Parker Aries AR-04CE - Regulatory Agencies; Standards of Compliance; Table 44 Regulatory Agencies

Parker Aries AR-04CE
129 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker Hannifin
Appendix C Regulatory Compliance–UL and CE - 111 -
Regulatory Agencies
The Aries Controllers are designed to meet the requirements of global
regulatory agencies. The drive/controllers have shown compliance with the
regulatory agencies in the following list. The list also shows additional steps
that must be taken to ensure compliance.
Agency Additional Steps User Must Take
UL Mains fuses
CE (LVD)
Mains fuses; earth connection for drive/controller and
motor (if applicable), proper installation
CE (EMC)
Varistors, mains filter, EMC cabling, EMC ready motor,
proper installation
Table 44 Regulatory Agencies
Standards of Compliance
UL
508C
CE for LVD
73/23/EEC
BS EN 61010-1
(1993) including
Amendment A2.
Safety requirements for electrical
equipment for measurement,
control, and laboratory use. Part
1. General Requirements.
CE for EMC
89/336/EEC
BS EN 61800-3
(1997) including
Amendment A11
Adjustable speed electric power
drive systems Part 3. EMC
product standard including
specific test methods.
BS EN 50081-2
(1994)
Electromagnetic
compatibility
Generic emission standard Part
2. Industrial Environment.
BS EN 61000-6-2
(1999)
Electromagnetic
compatibility Part 6-2:
Generic Standards
Immunity for industrial
environments.

Table of Contents

Related product manuals