Parker Hannifin
- 26 - Aries Controller Hardware Installation Guide
Inputs—High-Speed
The high-speed inputs are optically isolated inputs. Current is limited
internally for input voltage control of 5 to 24 volt logic. The Anode (+) and
Cathode () optocoupler inputs are on separate connector pins to allow
significant flexibility in wiring to different styles of interface.
Description Min Max Units
Turn-on time 200 ns
Turn-off time 400 ns
Guaranteed on voltage 4 VDC
Guaranteed off voltage 2 VDC
Maximum forward voltage 30 VDC
Maximum reverse voltage 30 VDC
Forward current 3 12 mA
Note: All parameters are at the connector pin.
Table 12 Inputs—Trigger and Home Electrical/Timing Characteristics
Inputs—General Purpose
These slow inputs are optically isolated. Current is limited internally for input
voltage control of 5 to 24 volt logic. The Anode (+) and Cathode ()
optocoupler inputs are on separate connector pins to allow significant
flexibility in wiring to different styles of interface.
Description Min Max Units
Turn-on time 1 ms
Turn-off time 2 ms
Guaranteed on voltage 4 VDC
Guaranteed off voltage 2 VDC
Maximum forward voltage 30 VDC
Maximum reverse voltage 30 VDC
Forward current 3 12 mA
Note: All parameters are at the connector pin.