Parker Hannifin
Chapter 3 Electrical Installation - 29 -
Power Supply
Input Power
The mains Motor Power supply and the optional Control Power supply for the
drive/controller must meet the requirements listed in Table 17.
Input Power Requirements
Motor Input Power (L1, L2) 120/240 VAC, 50/60 Hz, single phase
Control Input Power (C1, C2) 120/240 VAC, single phase
Table 17 Input Power Requirements
Fuse Requirements
Aries Controllers have no user-serviceable internal fuses. For safety, the
user must provide a fuse in each of the mains input lines.
Motor Power Fuse Information
Select the proper Motor Power input fuse for your specific application using
Table 18.
Drive AC Voltage Fuse Style Rating Fuse Type
120 VAC 125 VAC Time Delay 20A RK5 or better
AR-04CE
240 VAC 250 VAC Time Delay 20A RK5 or better
120 VAC 125 VAC Time Delay 20A RK5 or better
AR-08CE
240 VAC 250 VAC Time Delay 20A RK5 or better
120 VAC 125 VAC Time Delay 30A RK5 or better
AR-13CE
240 VAC 250 VAC Time Delay 30A RK5 or better
Table 18 Motor Power Fuse Information
Table 19 lists part numbers (at time of publication) for suitable fuses from
several man
ufacturers. These fuses are type RK5 (time delay fuses).
Amps Bussmann
Ferraz Shawmut
(formerly Gould)
Littelfuse
10 FRN-R-10 TR10R FLNR10
20 FRN-R-20 TR20R FLNR20
30 FRN-R-30 TR30R FLNR30
40 FRN-R-40 TR40R FLNR40
Table 19 Fuse Part Numbers
Important — Power to the Aries Controller can be supplied in two ways.
Completely read this section and comply with all safety measures before
proceeding with connecting the unit to power.