Brake Relay (Optional)
The Brake Relay connection (on the Output Power connector) provides a
safety feature for your motion control system, particularly for vertical
applications. The drive/controller acts as a control switch for the motor brake
(if a brake is present). When 24V is applied from an outside power supply
through the drive’s Brake Relay (BK) terminals, the motor brake is disabled.
When the power supply is interrupted, or the drive/controller faults or is
disabled, the brake is enabled and stops shaft rotation.
Brake Relay Connector (on Output Power Connector)
AR-04CE, AR-08CE, & AR-13CE
Connector Type.......................................Removable screw terminal
Terminals ........................................6
Pitch ................... 0.200 in (5.08 mm)
Wire range .....................12-26 AWG
.......................................14-27 SWG
................................(0.12-3.30 mm
2
)
Wire strip length...... 0.310 in (8 mm)
Torque....7.0 in–lbs nom. (0.79 N-m)
Brake Relay Operation
Drive Condition Relay State
Enabled Closed (conducting)
Faulted Open
No AC power on L1 and L2* or
drive not enabled
Open
* Mains Control power on C1 and C2 does not affect the relay. With mains power applied
to C1 and C2, the relay remains open if AC power is not applied to the L1 and L2
terminals.
Table 21 Brake Relay Operation
Brake Relay Specifications
Relay Type .............................................. Solid State Relay
Normally open
Relay Maximum Rating........................... 1 Amp at 24 VDC
Warning — Do not exceed the ratings of the brake relay. If required,
control a suitable external relay with this relay to meet your power
requirements.