4.6 Alarms management
4.6.1 Digital input alarms
ID CODE LED DESCRIPTION RESET
ID1
HPI
L5
High pressure alarm from pressure
switch
M
ID2
LPI
L6
Low pressure alarm from pressure
switch
M
ID3
tP
L7 Pump thermal cutout alarm M
ID4
LL
L8
Water tank low water level alarm / No
water ow
A
ID6
PII
L9
Compressor protection alarm /
Phases monitor
M
4.6.2 Allarmi da ingressi analogici
AI CODE DESCRIPTION RESET
B1
HAI
Tank water outlet water high tempera-
ture alarm
Warning
LAI
Tank water outlet water low tempera-
ture alarm
A
StI
Sensor open circuit or short circuit M
B2
HA2
Evaporator water outlet water high
temperature alarm
Warning
LA2
Evporator water outlet water low tem-
perature alarm
A
St2
Sensor open circuit or short circuit M
B3
HA3
High ambient temperature warning Warning
LA3
Low ambient temperature warning Warning
St3
Sensor open circuit or short circuit M
4.7 Automatic restart
In the event of a power failure, when power is restored the chiller will
assume theOn-Off statusheld at themoment the power was lost.
5 Maintenance
a) The machine is designed and built to guarantee continuous opera-
tion; however, the life of its components depends on the mainte-
nance performed.
b) When requesting assistance or spare parts, identify the machine
(model and serial number) by reading the dataplate located on the
unit.
c) An example of this record sheet can be downloaded from the site:
www.polewr.com.
5.1 General instructions
! Before performing any maintenance, make sure the power to the
refrigerator is disconnected.
Y Always use the Manufacturer’s original spare parts: otherwise the
Manufacturer is relieved of all liability regarding machine malfunction-
ing.
Y In case of refrigerant leakage, contact quali ed and authorized
personnel.
Y The Schrader valve must only be used in case of machine mal-
function: otherwise any damage caused by incorrect refrigerant charg-
ing will not be covered by the warranty.
5.2 Preventive maintenance
To guarantee lasting maximum chiller ef ciency and reliability, carry out:
a)
Z every 6 months - clean the condenser ns and make sure
compressor electrical absorption is within the dataplate values;
b)
Z kit for maintenance (par.7.5)
• kit for maintenance;
• service kit;
• individual spare parts.
5.3 Refrigerant
Z Charging: any damage caused by incorrect charging carried out
by unauthorized personnel will not be covered by the warranty.
Y At normal temperature and pressure, the R407C refrigerant is a
colourless gas classi ed in SAFETY GROUP A1 - EN378 (group 2 uid
according to Directive PED 2014/68/EU);
GWP (Global Warming Potential) = 1774.
! In case of refrigerant leakage, air the room.
5.4 Dismantling
The refrigerant and the lubricating oil contained in the circuit must be
recovered in conformity with current local environmental regulations.
%
Recycling
Disposal
frame and panels steel/epoxy resin polyester
tank aluminium/copper/steel
pipes/collectors copper/aluminium/carbon steel
pipe insulation NBR rubber
compressor steel/copper/aluminium/oil
condensator steel/copper/aluminium
pump steel/cast iron/brass
fan aluminium
refrigerant R407C (HFC)
valve brass/copper
electrical cable copper/PVC