EasyManua.ls Logo

Parker PSD04 - Page 71

Parker PSD04
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDE364
page 71 of 74
Power supply 0-20 mA/4-20 mA/0-10 V transducers: 12 VDC
±10%, 60 mA max.
Power supply 0-5 V ratiometric transducers: 5 VDC ±5%, 40 mA
max.
The device incorporate a restorable thermal protection of the power
supplies against the short circuit and the overload.
Digital inputs:
3 inputs of which 2 inputs (non optoisolated free of voltage
contacts, which can be set via configuration parameter as normally
open/normally closed contact) which can be set via configuration
parameter as enable the operation/change parameters
set/resynchronization command/backup module status and 1 input
(optoisolated high voltage contact, which can be set via
configuration parameter as normally open/normally closed contact)
which can be set via configuration parameter as enable the
operation/change parameters set/resynchronization
command/backup module status (not available in model PSD4BX3).
Non optoisolated free of voltage contacts
Power supply: none (5 V when not loaded, 3.3 mA
when loaded).
Protection: none.
Optoisolated high voltage contact
Power supply: 115 VAC -10%... 230 VAC +10%.
Protection: none.
The device ensure a reinforced isolation among each terminal of
the high voltage contact and the remaining parts of the device.
Displays:
PSD4BX3 PSD4BM3 PSD4BF3 PSD4DF3
signalling LEDs.
128 x 64 pixel
single colour
(black with
rearlighting
through white
LEDs) LCD
graphic
display,
signalling
LEDs.
Digital outputs:
1 SPST 5 res. A @ 250 VAC (5 res. A @ 30 VDC) output
(electromechanical relay) which can be set via configuration
parameter as alarm output/solenoid valve/resynchronization valve.