EasyManua.ls Logo

Parker PSD04 - Page 72

Parker PSD04
74 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDE364
page 72 of 74
Electromechanical relay
Maximum switching power: 1,250 VA (150 W).
Mechanical life: > to 5,000,000 operations.
Electrical life: > to 100,000 operations.
Protection: none.
The device ensure a reinforced isolation among each terminal of
the digital output and the remaining parts of the device.
Bipolar stepper motor output:
4 wires bipolar stepper motor output.
Bipolar stepper motor output
Input voltage: 21 VDC ±10%.
Output voltage: 27... 36 VDC (18... 24 VDC if
supplied by the backup module).
Maximum output current: 1 A.
Driver type: chopper (constant current).
Protection: none.
Type of actions and additional features: 1C.
Communication ports:
PSD4BX3 PSD4BM3 PSD4BF3 PSD4DF3
1 non
optoisolated
programming
port with
MODBUS
communication
protocol.
2 non
optoisolated
ports of which
1 RS-485 port
with MODBUS
communication
protocol and 1
programming
port with
MODBUS
communication
protocol.
3 non optoisolated ports of
which 1 CAN port with CANBUS
communication protocol, 1
RS-485 port with MODBUS
communication protocol and 1
programming port with
MODBUS communication
protocol.
Power supply remote user interface: 22... 35 VDC, 100 mA max.

Table of Contents