192-011004N5 PSD1-S Short Description 2017-08
192-011004N5 DOC-0002-01-R014 14.08.17 09:41 11
(20)
3.1.7. Control requirements
Use only with aligned controller (to avoid control loop oscillation).
3.1.8. Accessories
Make sure to use only the accessories recommended by Parker.
3.1.9. Notes on the use in domestiv environments
This is restricted operation category product according to EN 61800-3. This product
can cause high-frequency disturbance in domestic areas. Users are asked to take
suitable action if this proves to be the case.
3.2 Conditions of utilization for UL certification of PSD1-S
In this chapter you can read about:
UL certification ............................................................................................................. 11
Installations- & Environmental Characteristics PSD1-S ................................................ 11
Tightening torque of the wiring terminals ...................................................................... 12
Auxiliary connection electrical ratings ........................................................................ 13
Data of integrated dynamic brake unit .......................................................................... 13
In- / Output Ratings ...................................................................................................... 13
3.2.1. UL certification
Category
Specifications
Certified
E-File_No.: E235342
The UL certification is only valid if the type plate of the device shows the "UL" -sign.
PSD1-S:
UL61800-5-1 1st Edition, issued June, 8th, 2012
C22.2 No.274-13, 1st Edition, issued March, 2013
3.2.2. Installations- & Environmental Characteristics PSD1-S
Risk of Electric Shock, wait at least 3 minutes before removing cover
Use in Pollution degree 2 Environment.
Maximum Surrounding Air Temperature 40 °C.
The devices must be appropriately protected (e.g. by a switching cabinet). - Open
type equipment.
Use 60/75°C wires only
Use Copper Conductors Only
Do only use the Parker cables available under Accessories or assemble the
cables according to the specified regulations.
Control voltage supply (24 VDC) only permissible with "class 2" power supply.
Grounding Terminals - the screw terminals are suitable for Field Wiring
Connection only when the wire is provided with Eyelet Tube Terminal.
Overvoltage category III.
Short circuit ratings SCCR = 5000 Arms
The drive modules are equipped with a current limit. Values for maximum device
current and maximum motor current can be set via PSD ServoManager (Chapter
resp. Menu Limit values & Motor Characteristics).
Integral motor overload protection is not available.
The drive does not incorporate internal overload protection for the motor load and
this overload protection shall be provided in the end use applications.
Motor over temperature sensing is not provided by the drive