Conditions of utilization
192-011004N5 DOC-0002-01-R014 14.08.17 09:41
• Integral solid state short circuit protection does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the
Manufacturer Instructions, National Electrical Code and any additional local codes
• Suitable for use on a circuit capable of delivering not more than 5000 rms
Symmetrical Amperes, 240 Vac maximum. When protected by Listed – Cartridge
Fuses, Non-Renewable (JDDZ), Time-Delay Class-CC Fuses, rated 600 Vac, 3 A or
8A (for model No. PSD1SW1200) / 6 A or 12A (for model No. PSD1SW1300). See
table below for the manufacturers, model number and electrical ratings.
External Branch Circuit Protection
Time-Delay "Class-CC" Fuses
Listed – Cartridge Fuses, Non-Renewable manufactured by
Cooper Bussmann LLC (E4273)
(200 kARMS Symmetrical A.I.C.)
600 3 phases
Alternate External Branch Circuit Protection
Time-Delay "Class-CC" Fuses
Listed – Cartridge Fuses, Non-Renewable manufactured by
Mersen USA Newburyport-MA LLC (E2137)
(200 kARMS Symmetrical A.I.C.)
600 3 phases
For use in Canada:
• External Surge Protection devices (required in the end use instalation) - According
to the Canadian Standard C22.2-No.274-13.
• R/C Surge-Protective Device (VZCA2/8) and CSA-Certified transient surge
suppression shall be installed on the line side of this equipment and shall be
rated minimum 240 V (phase to ground), suitable for “Overvoltage Category III”,
and shall provide protection for a rated Impulse withstand Voltage peak of 4 kV.
3.2.3. Tightening torque of the wiring terminals
DSL® feedback / motor brake
ferrule with plastic sleeve
ferrule with plastic sleeve