192-011004N5 DOC-0002-01-R014 14.08.17 09:41
For further information please refer to Help file.
6.1 Mains connection PSD1-S
30 ... 253 VAC / 50-60 Hz
Single Phase 230 VAC ±10%
30 ... 253 VAC / 50-60 Hz
(1AC230V): 6.8 Arms
3AC230V: 1.7 Arms
(1AC230V): 11 Arms
3AC230V: 4.2 Arms
Single phase: 8 A / Three phases: 3 A
Fuse Class: gS (gRL), Time-delay
Single phase: 12 A / Three phases: 6 A
Fuse Class: gS (gRL), Time-delay
Circuit breakers for operation according to CE.
Circuit breakers for UL und CSA see
(see on page 11).
6.2 Control Voltage 24 VDC PSD1-S
Requirement according to
safe low voltage (SELV)
yes (class 2 mains module)
+ Output current of digital output currents (fed via connectors X17/2, 3)
+ Output current of motor brakes (fed via connectors X51/1 & 2))
+ Current requirements of optional boards
Dimensions
Height x Width x Depth (mm]
6.4 Environmental requirements PSD1
General ambient
conditions
In accordance with EN 60 721-3-1 to 3-3
Climate (temperature/humidity/barometric pressure): Class 3K3
<=1000m above sea level for 100% load ratings
<=2000m above sea level for 1% / 100m power reduction
please inquire for greater elevations
Type of protection IP20 according to EN 60 529
Degree of contamination 2 in accordance with EN 60664-1 and EN 61800-5-1