2.11 Before commissioning the drive, please observe the following:
Read the safety instructions.
Make sure that all local electrical regulations are adhered to.
Inspect the device for any damages.
Inspect the device within the drive and system for loose ends, blends, grinding- or
drilling chips, etc.
Check all external power circuits of the system: Power supply, control, motor and
ground connections.
Make sure no damages or injuries may occur by a rotating motor. Uncouple the
load from the motor shaft.
Check the condition of the motor thermistor- and brake resistance connections.
Make sure that all external set speeds are zero.
Make sure nobody works with another part of the system which may affect
switch-on.
Make sure that switch-on does not negatively influence other devices.
Verify if the motor connections are correctly wired.
Ensure that the STO function is not activated.