100 µF per kW of the temporal medium value of the total power (transmissions +
power dissipation) in the axis system.
Example: PSD1-M_P020 (1175 µF) with one axis controller (440 µF)
Total power 15 kW, 100 µF/kW => 1500 µF required in the axis system.
Axis system: 1615 µF are sufficient.
Connection of a braking resistor on PSD1-M_P (mains module)
Minimum line cross section:
2
Maximum intermediate circuit voltage:
Depending on the position of the
switches on the power module (see
5.12.8.1 Temperature switch mains module X40
Connector X40 Pin T1R, T2R
Temperature monitoring:
The temperature switch (normally closed contact) must be connected, unless an
error message will be issued.
Temperature switch/relay
No galvanic separation, the temperature sensor (normally closed contact) must
comply with the safe separation according to EN 60664.
If there is no temperature monitoring due to the connected braking resistor, the
T1R and T2R connections must be connected by a jumper.
Caution!
Without temperature monitoring, the braking resistor might be destroyed.
5.12.9. X4: Inputs / Outputs of the mains module
+24 VDC output (max. 340 mA)
24 VDC supply for outputs 0 ... 3
Enable (High=Enable, Low=Disable)
Ready (High=ready , Low=not ready )
Warning (High = no warning , low = warning)*
Axes must only be energized if A0 = ready = high!
Capacity utilization of DC Bus = 90%
Temperature alarm: Rectifier 5 K to switch-off threshold