EasyManua.ls Logo

PDC spas Owner's Manual - Accent Control Reminders; Maintenance Reminders

Default Icon
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operang System, LifeStyle Series | Accent™ Control
58
Once the GFCI is tripped manually, reset the GFCI and the spa will operate normally from that point.
Warning: The end-user must be trained to expect this one-me test to occur and how to properly reset the GFCI or RCD. If freezing
condions exist, the GFCI or RCD should be reset immediately or spa damage could result.
General
Priming Mode—M019
Each me the spa is powered up, it will enter Priming Mode. The purpose of Priming Mode is to allow the user to run each pump
and manually verify that the pumps are primed (air is purged) and water is flowing. This typically requires observing the output of
each pump separately, and is generally not possible in normal operaon. Priming Mode lasts 4 minutes, but you can exit it earlier
by pressing any Temp buon. The heater is not allowed to run during Priming Mode.
Water Temperature is Unknown
Aer the pump has been running for 1 minute, the temperature will be displayed.
Too Cold – Freeze Protecon
A potenal freeze condion has been detected and pump is acvated. The pump is ON for at least 4 minutes aer the potenal
freeze condion has ended. In some cases, pumps may turn on and off and the heater may operate during Freeze Protecon. This
is an operaonal message, not an error indicaon.
Water is too Hot (OHS) – M029
The system has detected a spa water temp of 110°F (43.3°C) or more, and spa funcons are disabled. System will auto reset when
the spa water temp is below 108°F (42.2°C). Check for extended pump operaon or high ambient temp.
Heater-Related
Heater Flow is Reduced (HFL) – M016
There may not be enough water flow through the heater to carry the heat away from the heang element. Heater start up will
begin again aer about 1 min. See “Flow Related Checks” below.
Heater Flow is Reduced (LF)* – M017
There is not enough water flow through the heater to carry the heat away from the heang element and the heater has been
disabled. See “Flow Related Checks” below. Aer the problem has been resolved, you must press any buon to reset and begin
heater start up.

Related product manuals