EasyManua.ls Logo

Pentair AUTOTROL MAGNUM 742 - Basic Programming Mode Chart 742 F-762 F;293 Valve Type

Pentair AUTOTROL MAGNUM 742
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installer Manual Magnum 742-762 - Programming
Ref. MKT-IM-012 / C - 25.10.2019 49 / 106
6.3.2. Basic programming mode chart 742F-762F/293 valve type
Parameter description Range of values
Default
value
Units of
measure
Notes
Program valve type
255, 263, 268,
278 and
Magnum series
None N/A -
Program system size 5 - 100 / F None liters -
Time setting
1:00 - 12:59 AM
0:00 - 23:59 PM
12:00 PM
hour:
minute
-
Day of week N/A None N/A -
Time of backwash
1:00 - 12:59 AM
0:00 - 23:59 PM
12:00 PM
hour:
minute
Dependent of time setting (AM
or PM).
Days override
(762F controller only)
0.5 - 99 0 day
0 = no days override.
0.5 = regeneration twice a day
at time of regeneration and
12 hours later.
Days between
regeneration
(742F controller only)
0.5 - 99 0 day
0 = no days between
regeneration.
0.5 = regeneration twice a day
at time of regeneration and
12 hours later.
Backwash length 0 - 200 14 minute -

Table of Contents