EasyManua.ls Logo

Pentair AUTOTROL MAGNUM 742 - Basic Programming Parameters (3 - Cycle Filter System)

Pentair AUTOTROL MAGNUM 742
106 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installer Manual Magnum 742-762 - Programming
Ref. MKT-IM-012 / C - 25.10.2019 57 / 106
6.4.3. Basic programming parameters (3 - Cycle filter system)
* Default value selected with valve type and resin volume.
Parameter description Range of values
Default
value
Units of
measure
Notes
P1 Time of day
1:00 - 12:59AM
0:00 - 23:59PM
12:00 PM
Hour :
minute
Range depends on value
selected for P10.
P2 Day of week N/A None N/A -
P3
Time of
regeneration
1:00 - 12:59AM
0:00 - 23:59PM
2:00 AM
Hour :
minute
Range depends on value
selected for P10.
P4 Calendar override 0 - 99 3 Days
0 = no calendar override.
0.5 = regeneration twice a day
at time of regeneration and 12
hours later.
Calendar override skipped if at
least one day of regeneration
selected.
P5
Day of week
regeneration
N/A None N/A
Day of week regeneration is
skipped if calendar override is
more than 0 (742 controller
only).
P6 Backwash time 1 - 250 14 Minutes -
P7 Capacity of unit 1 - 900 *
m
3
Unit of measure depends on
value selected for P9.
P8 - - - -
Skipped for 3 - cycle filter
configuration.

Table of Contents