Installer Manual Magnum 742-762 - Programming
58 / 106 Ref. MKT-IM-012 / C - 25.10.2019
6.4.4. Advanced programming parameters (3 - Cycle filter system)
* Default value selected with valve type and resin volume.
** Factory default value is "0" for North America and "1" for World units.
Note
Parameters P16 to P19 are skipped on 742 controller.
Parameter description Range of values
Default
value
Units of
measure
Notes
P9 Units of measure 0 - 1 ** N/A
0 = US unit.
1= Metric unit.
P10 Clock mode 0 - 1 ** N/A
0 = 12 hour clock.
1 = 24 hour clock.
P11 Service interval 0 - 250 0 Months Uses 30 days for each months.
P12
Remote
regeneration
3 - 250 60 Seconds
Time remote switch must be
active to start regeneration on
742 controller.
P13 - - - -
Skipped for 3 - cycle filter
configuration.
P14 - - - -
Skipped for 3 - cycle filter
configuration.
P15 - - - -
Skipped for 3 - cycle filter
configuration.
P16 Reserve type 0 - 3 0 N/A
0 = variable reserve delayed
regeneration.
1 = fixed reserve delayed
regeneration.
2 = variable reserve immediate
regeneration.
3 = fixed reserve immediate
regeneration.
P17
Initial average or
fixed reserve
0 - 70 30
% of
capacity
Depends on value selected for
P16.
P18 Flow sensor select 0 - 5 * N/A
0 = internal Magnum NHWB.
1 = 1" Autotrol turbine.
2 = 2" Autotrol turbine.
3 = User defined.
K-factor,
4 = User defined pulse
equivalent.
5 = internal Magnum HWB.
P19
K-factor or
pulse equivalent
1.00 -99.99
0 - 9999
0.01
1
N/A
K-factor P18 = 3.
Pulse equivalent P18 = 4.