FLECK 2750 Downflow Service Manual 35
GENERAL SERVICE HINTS FOR METER
CONTROL
Problem: Softener delivers hard water
Reason: Reserve capacity has been exceeded.
Correction: Check salt dosage requirements and reset
program wheel to provide additional reserve.
Reason: Program wheel is not rotating with meter output.
Correction: Pull cable out of meter cover and rotate manually.
Program wheel must move without binding and clutch must
give positive clicks when program wheel strikes regeneration
stop. If it does not, replace timer.
Reason: Meter is not measuring flow.
Correction: Check meter with meter checker.