Installer Manual Fleck 2910 - NXT - Programming
60 / 114 Ref. MKT-IM-002 / B - 23.05.2018
FEED WATER
HARDNESS
1 to 1’999
Milligram CaCO
3
/L
This screen will only display on the
lead unit for system types 6 & 7. For all
other system types, it will display for
all units.
Use the SHIFT button to move to the
left.
TRIP POINT 1 1 to 3997 L/m This screen will only display for system
14 and will only appear on the master
controller (Valve address #1).
Use the SHIFT button to move to the
left.
TRIP DELAY 1 30 to 99
Second
(30 seconds default)
TRIP POINT 2 1 to 3997 L/m This screen will only display for system
14 and will only appear with the system
sized to 3 or 4 on the master controller
(Valve address #1).
Use the SHIFT button to move to the
left.
TRIP DELAY 2 30 to 99
Second
(30 seconds default)
TRIP POINT 3 1 to 3997 L/m This screen will only display for system
14 and will only appear with the system
sized to 4 on the master controller
(Valve address #1).
Use the SHIFT button to move to the
left.
TRIP DELAY 3 30 to 99
Second
(30 seconds default)
REGENERATION
DAY OVERRIDE
OFF to 99 Day
Days between regenerations for
timeclock mode.
REGENERATION
TIME
00:00:00 to
23:59:59
Hour
Regeneration time will not appear
unless regeneration day override or
timeclock is on.
CYCLE 1
OFF to
04:00:00
CYCLE 2
OFF to
04:00:00
CYCLE 3
OFF to
04:00:00
CYCLE 4
OFF to
04:00:00
Parameter Options Definition Note