Installer manual Fleck 5600 SXT - Programming
62 / 104 Ref. MKT-IM-013 / E - 23.09.2020
Info
Setting a cycle step to0 will cause the controller to skip that step during regeneration,
but keeps the following steps available.
The different regeneration cycles are listed in sequence based on the regeneration
flow selected for the system.
All cycles can be set from0 to 199 minutes.
6.5.14.1 Regeneration abbreviations
B1 First backwash BF Brine fill
B2 Second backwash BW Backwash
BD Brine draw RR Rapid rinse
6.5.14.2 For pre-set regeneration cycles
1. Press or to set the regeneration cycle time.
2. Press to validate the selection and move to the next parameter.
3. Repeat the two previous steps for each cycle.
6.5.15 Day of week (Dn, n=1 to7)
Set the day of week for regeneration.
Info
The day of week parameter is only available if "day" mode has been set in controller
type selection.
1. Press or to set "ON" or "OFF" to set the day as a regeneration
day.
2. Press to validate the selection.
3. Repeat the two previous steps until D7 is set.
4. Press to validate the selection and move to the next parameter.
6.5.16 Current day (CD)
Set the current day.
Info
The current day is defined from D1(Monday) to D7(Sunday).
1. Press or to set the current day.
2. Press to validate the selection and move to the next parameter.
6.5.17 Flow meter type (FM)
Select the flow meter type.