Installer manual Fleck 5600 SXT - Programming
Ref. MKT-IM-013 / E - 23.09.2020 63 / 104
Options:
P0.7: ¾" paddle wheel meter (Standard setting for 4600, 5600 and 9100);
t0.7: ¾" turbine meter;
P1.0: 1" paddle wheel meter (Standard setting for 2750 and 9000);
t1.0: 1" turbine meter;
P1.5: 1½" paddle wheel meter (Standard setting for 2850);
t1.5: 1½" turbine meter;
P2.0: 2" paddle wheel meter;
Gen: generic or other non-Fleck meter.
1. Press or to set the flow meter type.
2. Press to validate the selection and move to the next parameter or exit
master programming mode and save modifications done.
6.5.18 Meter pulse (K)
Set the meter pulse for a non-standard flow meter.
Info
The meter pulse parameter is only available if the Gen option has been set in flow
meter type selection.
1. Press or to set the meter constant in pulses per unit of volume.
2. Press to validate the selection and to exit the master programming
mode.
6.6 Filter programming
To use the valve as a filter, in the master programming mode, set the regeneration flow(VT) to
filter(FLtr). The controller will let set only the steps necessary to the filter mode, which are:
regeneration control type(CT), days override(DO), regeneration time(RT), backwash(BW), rapid
rinse(RR), day of week(Dn) and current day(CD).
6.7 Diagnostic
Info
Depending on current settings, some displays cannot be viewed.
If none of the buttons are pushed for 1minute in the diagnostic mode the controller
returns to Service mode.
6.7.1 Commands
1. Press and hold and for fiveseconds to enter the diagnostic mode.
2. Press or to navigate in the diagnostic mode.
3. Press to exit the Diagnostic mode at any time.