Installer manual Fleck 5600 SXT - Programming
Ref. MKT-IM-013 / E - 23.09.2020 65 / 104
6.7.7 Software version (SV)
Info
Shows the version of the software used by the controller.
1. Software version display:
6.8 Resetting the controller
Mandatory
Once you have completed this operation, check all programming steps!
Info
There are two options to reset: partial and hard reset.
Partial reset will set all the parameters to default values, except volume remaining in
volumetric systems and days since last regeneration in time clock systems.
Hard reset will set all the parameters to default values.
6.8.1 Soft reset (SR)
1. Press and hold and for 25seconds while in normal service mode
until SR is displayed.
2. Reprogram all parameters in Master programming mode.
6.8.2 Hard reset (HR)
1. Hold while powering up the unit.
2. The display shows HR.
3. Reprogram all parameters in Master programming mode.