EasyManua.ls Logo

Pentair Fleck 5800 LXT - Commands; Setting the Time of the Day; Master Programming; Master Programming Mode Chart

Pentair Fleck 5800 LXT
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installer manual Fleck 5800 LXT - Programming
50 / 96 Ref. MKT-IM-005 / F - 30.04.2020
6.2 Commands
1. Press MODE to pass to the next programming option.
2. Press and hold or until the Time of Day icon appears.
3. Use and to adjust the values.
4. Press and hold until the Programming icon disappears to save your programming.
6.3 Setting the time of the day
1. Press MODE until display position point to the Time of Day icon.
2. Press and hold or until the Programming icon appears.
3. Set the time with or .
4. Press and hold to validate the selection and return to the service
mode.
6.4 Master programming
6.4.1 Master programming mode chart
Parameter Options Definition Note
Amount of resin 0-115/F L -
Salt amount 50-290 g/L Only for softening systems
Water hardness 30-2000 mgL Only for softener meter delayed
Days between
regen
1-30 Day Only for softener time clock delayed
Backwash
lenght
1-30 Minute Only for filter
6.4.2 Setting the amount of resin in the tank
Info
Setting the amount of resin in the tank must be done first. Anytime this parameter is
changed, other parameters (salt dosage, water hardness,...) will be reset to default
value.
1. Press MODE until display position point to the Resin icon.
2. Press and hold or until the Programming icon appears.
3. Set the volume of resin with or , 5 to 115l(metric).
4. Press and hold to validate the selection and return to the service
mode.