Installer Manual Fleck 5800 - XTR - Programming
64 / 122 Ref. MKT-IM-006 / B - 16.01.2018
Valve
Volume
override
1 to 999 999 999
gallons/liters
Only displayed when regeneration type is filter
immediate or filter delayed.
Regeneration
Regeneration
flow
Downflow
Downflow 2x BW
Upflow
Custom Downflow
Custom Upflow
Variable Refill
Filter
Custom Filter
Cycle steps on the home screen and during
regeneration will change to reflect the cycle
steps and order in the selected regeneration
flow.
Additional regeneration screen parameters
are dependent upon selected regeneration
flow. Not all parameters will be displayed,
depending of the selected regeneration flow.
Custom upflow, downflow and filter allows for
up to 20 programmable cycle steps.
Variable refill calculates refill time based on
salt dosage, media volume, and BLFC Size,
and it is not possible to change it.
Time per cycle step can be programmed for
all other regenerant flow options.
Relay output Aux.1/Aux.2
Alarm Based
Cycle Based
Time Based
Volume Based
Off
For cycle based relays, select the cycle steps
on which the relays will turn on. For time
based relays, two start/end times can be
selected for each relay. Relay times are based
on total regeneration cycle time.
Volume based relays can be programmed
from one gallons/liters to the full system
volume capacity. Duration can be set from one
second to two hours. Volume based option is
not available when regeneration type is set to
time clock. Alarm based relays will turn on
when an alarm condition is met, and will turn
off when the alarm is cleared.
Meter Meter type
0.75" Paddle
1.00" Paddle
1.25" Turbine
1.50" Paddle
1.50" Turbine
2.00" Paddle
3.00" Paddle
Generic
Only available when meter regeneration type
is selected.
Select the type of meter installed with the
system. A generic option is available if the
installed meter does not match any other
selection. Selecting the generic meter type
requires setting the number of pulses per
gallon or liter to ensure proper metering.
The standard setting for 5800-XTR is 0.75"
Turbine.
Screen name Parameters Values Notes

Table of Contents