Installer Manual Foleo - Installation
32 / 112 Ref. MKT-IM-038 / C - 15.11.2019
4.5.6. Water supply line and bypass connections
4.5.6.1 Water supply line
The connections should be hand tightened using PTFE (plumber’s tape) on the threads if using the
threaded connection type.
In case of heat welding (metal type connection), the connections should not be made to the valve when
soldering.
NOTE
See chapter 3.4. Description and components location, page 23 to identify the connections.
When pressurized, any composite tank will expand both vertically and circumferential. In order to
compensate the vertical expansion, the piping connections to the valve must be flexible enough to
avoid overstress on the valve and tank.
In addition, the valve and tank should not be supporting any part of the piping weight. This is hence
compulsory to have the piping fixed to a rigid structure (e.g. frame, skid, wall…) so that the weight of
it is not applying any stress on the valve and tank.
The diagrams above illustrate how the flexible piping connection should be mounted;
in order to adequately compensate the tank elongation the flexible tubes must be installed
horizontally;
should the flexible piping connection be installed in vertical position, instead of compensating
the elongation, it will create additional stresses on the valve & tank assembly. Therefore this is
to be avoided;
the flexible piping connection must be also be installed stretched, avoiding excessive length. For
instance 20 - 40 cm is enough;
200 mm flexible
Support to the wall