Step 5: Review the Fail Safe setting
Fig. 2.13 Setup|Circuit window and Fail Safe button
At the Setup|Circuit window:
Pressing the Fail Safe toggle button alternates the Fail Safe mode between Power Off and
Power On. This selection tells the NGC-30-CRM/-CRMS if the heater should be turned on or off
if all of the RTD(s) for this Circuit fail.
If the main concern is to prevent pipes from freezing, then Power On is a good choice. However,
if the heater is oversized and overheating is a concern, then Power Off could be a better choice.
Step 6: Go to Setup | RTDs window
Fig. 2.14 Setup | RTDs window