EasyManua.ls Logo

Pentair raychem ngc-30/uit2 - Page 20

Pentair raychem ngc-30/uit2
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 / 84
industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H5818602/16
At the Setup|RTD window:
The Raychem NGC-30 program first checks to see if the default RTD is available. On any
NGC-30-CRM/-CRMS board, the first RTD input is automatically coupled with the first relay
output; the second RTD is linked with the second output relay, etc. (In the case an RMC - RMM2
combination is chosen, then the user must define himself which RTD Device address is coupled
with the RMC output.)
Here an RTD has been connected to the RTD 1 terminal block, so the RTD set-up window
indicates the default assignment is already completed.
There are three blank slots available so you can assign additional RTDs to this output relay. You
may desire additional RTDs if you need a more exact temperature sampling for a temperature-
sensitive fluid. If you assign additional RTDs, the lowest RTD value from the list will be used for
control temperature.
Each of the four RTDs can be independently set as Control or Monitoring only sensor. If you are
using a PLI module with SES-CONT sensors, an additional Continuity mode will be available.
See Section 3 for more details.
See page 33 for information on how to set up additional RTDs. For this simple Circuit Quick
Start example, the default set-up RTD is used.
Step 7: Go to the Setup | Temp window
Fig. 2.15 Setup | Temp window
At the Setup|Temp window:
Input the Setpoint, Dead Band, High Temp Alarm, and Low Temp Alarm by pressing on each of
the four numeric fields in turn.
For this example, the Setpoint temperature is 10°C, a dead band of 3°C and high and low
temperature alarms at 149°C and -12°C respectively.
Use the default value of 900 seconds (15 minutes) for the Temperature Alarm Filter (time delay
before the NGC-30 reports any temperature alarm) and the default value of Disable for the High
Temp Cut-Out. To implement the High Temp Cut-Out feature. See “High Limit Cut-Out Entry
Field” on page 36.

Table of Contents

Related product manuals