industrial heat tracing solutions
EN-RaychemNGC30UIT2Programming-AR-H5818602/16
Step 8: Go to Setup | Electrical
Fig. 2.16 Setup | Electrical
At the Setup | Electrical:
Input the Ground-Fault Current Alarm and Ground-Fault Current Trip by pressing each of the
two numeric fields in turn.
For this example, the Ground-Fault Current Alarm and Ground-Fault Current Trip levels are set
to 20 mA and 30 mA respectively.
At less than 20 mA, the Raychem NGC-30 program takes no action. At 20 mA or more
leakage, an alarm is indicated and logged to the Events List.
At 30 mA the output relay assigned to this Circuit is tripped off.
High Voltage Alarm Entry Screen
If the voltage monitoring module measures line voltage above this threshold, the NGC-UIT2
generates an alarm.
Range: 50 – 305 V
Default: 270 V
Low Voltage Alarm Entry Screen
If the voltage monitoring module measures line voltage below this threshold, the NGC-UIT2
generates an alarm.
Range: 50 – 305 V
Default: 90 V