Fig. 3.44 System|Comm window (RS-232 Host Configuration)
RTU Character Timeout Entry Field
This sets the time the NGC-UIT2 waits after last character is received before it determines that the
message has ended.
Range: 0–1000 milliseconds
Default: 25
Transmit Delay Entry Field
This sets the time the NGC-UIT2 will wait after it receives a message before it replies.
Range: 0-5000 milliseconds
Default: 0
Baud Rate Entry List
Allows you to select the baud rate of the external communication port.
Selection: 2400, 4800, 9600, 19200, 38400, 57600
Default: 9600
Stop Bits
Allows you to select the number of stop bits used.
Range: 1–2
Default: 2
Parity
Allows you to select what type of parity will be used.
Selection: None, Odd, Even
Default: None