Electrical 7
For parts or assistance, call Flotec Customer Service at 1-800-365-6832
Hazardous voltage. Can shock, burn, or kill.
Connect ground wire before connecting power supply
wires.
Use the wire size (including the ground wire) speci-
fied in the wiring chart. If possible, connect the pump to a
separate branch circuit with no other appliances on it.
Explosion hazard. Do not ground to a gas sup-
ply line.
WIRING CONNECTIONS
Fire hazard. Incorrect voltage can cause a
fire or seriously damage the motor and voids the warranty.
The supply voltage must be within ±10% of the motor
nameplate voltage.
NOTICE: Dual-voltage motors are factory wired for 230
volts. If necessary, reconnect the motor for 115 volts, as
shown. Do not alter the wiring in single voltage motors.
Install, ground, wire, and maintain your pump in com-
pliance with the National Electrical Code (NEC) or the
Canadian Electrical Code (CEC), as applicable, and with
all local codes and ordinances that apply. Consult your
local building inspector for code information.
Connection Procedure:
Step 1. Connect the ground wire as shown in Figure 11.
The ground wire must be a solid copper wire at
least as large as the power supply wires.
Step 2. There must be a solid metal connection between
the pressure switch and the motor for motor
grounding protection. If the pressure switch is
not connected to the motor, connect the green
ground screw in the switch to the green ground
screw under the motor end cover. Use a solid
copper wire at least as large as the power supply
wires.
Step 3. Connect the ground wire to a grounded lead in
a service panel, to a metal underground water
pipe, to a metal well casing at least ten feet (3M)
long, or to a ground electrode provided by the
power company or the hydro authority.
Step 4. Connect the power supply wires to the pressure
switch as shown in Figure 11.
Table I: Wiring Chart – Recommended Wire and Fuse Sizes
Branch Distance in Feet (Meters);
Max Fuse Wire Size AWG (mm
2
)
Load Rating 0-100 101-200 201-300 301-400 401-500
Model HP Amps Amps (0-30) (31-61) (62-91) (92-122) (123-152)
115Volts:
SLC 1/2 9.9 15 14(2) 10(5.5) 8(8.4) 8(8.4) 6(14)
HLC 1/2 12.4 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
SLD 3/4 12.4 20 12(3) 10(5.5) 8(8.4) 6(14) 6(14)
HLD 3/4 14.8 20 12(3) 8(8.4) 6(14) 6(14) 4(21)
SLE 1 14.8 20 12(3) 8(8.4) 6(14) 6(14) 4(21)
HLE 1 19.9 25 10(5.5) 8(8.4) 6(14) 4(21) 4(21)
SLF 1-1/2 19.9 25 10(5.5) 8(8.4) 6(14) 4(21) 4(21)
230 Volts:
SLC 1/2 4.9 15 14(2) 14(2) 14(2) 14(2) 12(3)
HLC 1/2 6.2 15 14(2) 14(2) 14(2) 12(3) 12(3)
SLD 3/4 6.2 15 14(2) 14(2) 14(2) 12(3) 12(3)
HLD 3/4 7.4 15 14(2) 14(2) 14(2) 12(3) 10(5.5)
SLE 1 7.4 15 14(2) 14(2) 14(2) 12(3) 10(5.5)
HLE 1 9.9 15 14(2) 14(2) 12(3) 10(5.5) 10(5.5)
SLF 1-1/2 9.9 15 14(2) 14(2) 12(3) 10(5.5) 10(5.5)