43
Installation and User’s Guide
The table below should be used by trained air-conditioning and refrigeration service people.
The table below should not be used for adjusting the charge in the system.
Use of interpolation or extrapolation of the table data may not be appropriate unless it is closely matched by
the ambient and water flow conditions.
Model
Discharge
Pressure
si
Suction
Pressure
si
Superheat
F
HP500
359 134 14
HP700
348 132 14
HP900
355 142 10
HP1200
367 141 8
HP1200R
367 141 8
UltraTem
110
343 164 11
UltraTem
120
350 157 9
UltraTem
120 H/C 378 157 10
UltraTem
120C 354 150 12
UltraTem
100I 340 154 10
UltraTem
90I 354 157 9
Model
Discharge
Pressure
si
Suction
Pressure
si
Superheat
F
HP500
352 125 11
HP700
341 123 11
HP900
348 132 8
HP1200
360 131 6
HP1200R
360 131 6
UltraTem
110
337 153 9
UltraTem
120
344 146 7
UltraTem
120 H/C
368 146 8
UltraTem
120C
346 143 10
UltraTem
100I
335 144 8
UltraTem
90I
335 152 8
Model
Discharge
Pressure
si
Suction
Pressure
si
Superheat
F
HP500 330 83 5
HP700 320 81 4
HP900
325 85 4
HP1200
322 86 3
HP1200R
322 86 3
UltraTem
110
324 92 4
UltraTem
120
330 90 3
UltraTem
120 H/C
336 90 3
UltraTem
120C
318 89 4
UltraTem
100I
329 86 4
UltraTem
90I
327 90 4
Model
Discharge
Pressure
si
Suction
Pressure
si
Superheat
F
HP500
457 137
7
HP700
445 142
8
HP900
450 141
5
HP1200
478 135
6
HP1200R
478 135
6
UltraTem
110
453 159 5
UltraTem
120
450 152 4
UltraTem
120 H/C
474 152 4
UltraTem
120C
450 150 7
UltraTem
100I
452 151 4
UltraTem
90I
473 150 6
RH = Relative Humidity
Air: 80F, 80%RH Water: 80F, 45-50gpm
Air: 80F, 63%RH Water: 80F, 45-50gpm
Air: 50F, 63%RH Water: 80F, 45-50gpm
Air: 80F, 63%RH Water: 104F, 45-50gpm