VisuNet FLX Panel
Product Description
Directive conformity
Electromagnetic compatibility
Directive
2014/30/EU
DIN EN 55035:2018-04
Explosion protection
Directive
2014/34/EU
EN IEC 60079-0:2018
EN IEC 60079-7:2015/A1:2018
EN 60079-11:2012
EN 60079-31:2014
RoHS
Directive
2011/65/EU
(RoHS)
EN IEC 63000:2018
Ambient conditions
Operating tem-
perature
Temperature classes:
A: 0 45 °C (32 113 °F)
B: -20 55 °C (-4 131 °F) [with wide temperature grade RAM/storage
and optically bonded display unit]
Storage tempera-
ture
-20 ... 65 °C (-4 ... 149 °F)
Relative humidity max. relative humidity 93% at 40°C (non-condensing) according to
EN60068-2-78
Climatic condi-
tions
Passive cooling, no rotating parts
Altitude Operating altitude max. 2000 m
Shock resistance 18 shocks 15 g, 11 ms all axis, IEC 60068-2-27
Vibration resis-
tance
10 ... 150 Hz, +/- 0.075 mm, 1 g, 10 cycles per axis according to EN60068-
2-6
Mechanical specifications
Degree of protec-
tion
Front side: IP66
Back side: IP20
Type 4X indoor
Material Front bezel: Stainless steel AISI304 (glass, silicone gasket)
Backside: Painted aluminum sheet metal
Installation Panel mount (additional Mounting Kits available) installed in boundary wall,
in cabinet wall or special enclosure
Mass 22GT, 22FC and 19SC: approx. 8 kg
15FC: 5.4 kg
Dimensions 22 inches: 567 mm x 358 mm x 68 mm
19 inches: 485.7 mm x 410.5 mm x 68 mm
15 inches: 434 mm x 283.4 mm x 67 mm
For cut out dimensions refer to chapter 4.4 Mounting the Panel Into the