DUS360CR Installation Instructions Rev A Specications subject to change without notice
Dynalite manufactured by WMGD Pty Ltd (ABN 33 097 246 921) Unit 6, 691 Gardeners Road Mascot NSW 2020 Australia Tel: +61 2 8338 9899 Fax: +61 2 8338 9333
E-Mail: support.controls@philips.com Web: http://philips.com/dynalite
DyNet Terminal 5-way pluggable screw terminal
1 x 2.5mm
2
conductor size
DyNet Network Supply
RS485 12-24 VDC, 20mA max
PIR sensor: Quad element pyroelectric
Max detection range
: 5 m
Detection area: 7.4 m x 5.6 m (at 2.4m mounting height)
Detection speed: 1 m/s
Detection object: 700 mm x 250 mm
Detection zones: 64
Activation indicator: LED
PE cell: <5 to >5000 lux (reected)
Automatic daylight harvesting mode
Infrared Rx: RC5
Controls:
Walk test / LED indicator
Network sign-on button
Compliance: CE, RCM
Operating Conditions: Temperature: 0 to 45° C ambient
Humidity: 0 to 90% non-condensing
Storage & Transport: Temperature: -25 to 60° C ambient
Humidity: 0 to 90% non-condensing
Construction: ABS plastic enclosure
Dimensions: 72 mm dia. x 41 mm (2.8” dia. x 1.6”)
Packed Weight: TBA kg
Installation Steps
1. Fix the sensor to a 64 mm diameter circular hole in a rm section of the ceiling. The mounting position should adhere to the following
guidelines:
•Ceiling height should be between 2.1 m and 4.0 m. Optimum height is 2.4 m.
•Position the sensor at least 1 m away from electrical lighting such as neon and uorescent lights.
•Avoid exposure to direct sunlight and heating/cooling sources.
•Position the sensor where pedestrian trafc is likely to move through the detection zone.
•Note that the sensor coverage area is rectangular, approximately 7.6 m x 5.4 m (at 2.4 m installation height).
•The detection range above is specied for an ambient temperature of 25ºC. This range is reduced at higher temperatures.
2. If needed, pull out and rotate the masking bezel to block a 120º viewing angle.
3. Terminate the DyNet cable as indicated below. If terminated and powered correctly, the red indicator LED turns on for 5 seconds.
Recommended Cable Type
Dynalite DYNET-STP-CABLE or equivalent
shielded three twisted-pair cable.
See datasheet for more information.
Recommended Cable Color Coding
Green/White Pair Paralleled for GND
Orange/White Pair Paralleled for +12VDC
Blue/White Pair Blue for DATA+
White for DATA-
Brown/White Pair Spare, use for SHIELD on unshielded cables
RS485 DyNet network