Completing ITS Installation Worksheets
IntelliVue Telemetry System Infrastructure Installation and Service Guide 2-29
APC Configuration Worksheet
Setting
Descriptions
Refer to the following setting descriptions when completing the Access Point
Controller Configuration Worksheet.
APC Configurations - In the worksheet provided, fill in the following information
for each APC to be added to the wireless subnet:
- APC Name - Name to be assigned to this APC within the system
- APC MAC - MAC Address documented on product label (physical address)
- APC IP Address - IP address for the APC within the wireless subnet
Subnet Mask - Set to subnet mask of the ITS wireless subnet. This will be
255.255.240.0 for Routed systems, and 255.255.248.0 for Non-Routed
systems.
Default Gateway - Typically this will be 172.31.240.1 for Routed systems, and
172.31 (n + 3).0 for Non-Routed systems.
Separate blank templates for non-routed and routed ICN topologies are provided on
the following pages.