12.2 Ordering data
12.2.1 Controller
12.2.2 Accessories
Conformity with EMC Directive 2014/30/EU
Immunity test according to EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/
IEC 61000-4-2
Criterion B
6 kV contact discharge
8 kV air discharge
Electromagnetic fields EN 61000-4-3
IEC 61000-4-3
Criterion A
Field strength: 10 V/m
Fast transients (burst) EN 61000-4-4/
IEC 61000-4-4
Criterion B
Supply lines: 2 kV
Signal/data lines: 2 kV
Surge test EN 61000-4-5
IEC 61000-4-5
Criterion B
Signal/data lines: 1 kV
Supply lines: 0.5 kV
Conducted disturbance variables EN 61000-4-6
IEC 61000-4-6
Criterion A
Test voltage: 10 V
Noise emission test according to EN 61000-6-3
Noise emission EN 55022 Class B
Approvals
For the latest approvals, please visit phoenixcontact.net/products.
Description Type Order No. Pcs. / Pkt.
Axiocontrol for the direct control of Axioline F I/Os. With 2 Ethernet interfaces
and programming capabilities according to IEC 61131-3. Complete with con-
nector and marking field.
AXC 1050 2700988 1
Axiocontrol for the direct control of Axioline F I/Os. With 2 Ethernet interfaces
and programming capabilities according to IEC 61131-3. Complete with con-
nector and marking field.
AXC 1050 XC 2701295 1
Description Type Order No. Pcs. / Pkt.
Axioline F bus base module AXL F BS BK 2701422 5
Axioline F short power connector (for devices such as AXL F BK, etc.) (re-
placement item)
AXL CN S/UL 2701421 5
AX OPC SERVER, communication interface for OPC-compatible visualiza-
tion with PC Worx-based controllers
AX OPC Server 2985945 1
Program and configuration memory, pluggable, 512 MB. SD FLASH 512 MB 2988146 1
Program and configuration memory, pluggable, 512 MB with license key for
function block libraries, e.g., for: SNMP, SQL, wireless, motion functions, etc.
SD FLASH 512 MB APPLIC A 2701799 1
Program and configuration memory, pluggable, 512 MB with license key for
licensing the PDPI-BASIC function block for precise multi-channel controllers
with self-optimization, e.g., for heating and cooling functions or hydraulic
movements.
SD FLASH 512MB PDPI BASIC 2701800 1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact AXC 1050 and is the answer not in the manual?

Phoenix Contact AXC 1050 Specifications

General IconGeneral
BrandPhoenix Contact
ModelAXC 1050
CategoryController
LanguageEnglish

Related product manuals