F_ADDR_XXXXX_ACK_REQ *) BOOL F-Device XXXXX requires an operator acknowledge request after
removing an error. Possible reasons for activating the operator
acknowledge request:
– Communication error (CRC, F_WD_TIME_OUT)
– Error in an F-Device. Please refer to the user documentation for
the F-Devices used.
F_ADDR_XXXXX_ACK_REI *) BOOL If F-Device XXXXX requires an operator acknowledge request, it can
be acknowledged by an operator acknowledge reintegration (F_AD-
DR_XXXXX_ACK_REI).
F_ADDR_XXXXX_DEVICE_FAULT *) BOOL Error in an F-Device.
If this variable was set to TRUE during operation, the cause of the error
must be removed first so that acknowledgment can be carried out
using the F_ADDR_XXXXX_ACK_REI or ACK_REI_GLOBAL vari-
able. If the cause has been removed, the F_ADDR_XXXXX_DEVICE
FAULT variable is set to FALSE again.
Table 8-6 Management/diagnostic variables for each configured F-Device
System variable Ty pe Meaning
For information on which errors cause the used F-Device
to control this variable, please refer to the device-specific
user documentation.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RFC 4072S and is the answer not in the manual?

Phoenix Contact RFC 4072S Specifications

General IconGeneral
BrandPhoenix Contact
ModelRFC 4072S
CategoryController
LanguageEnglish

Related product manuals