EasyManuals Logo

Phoenix Contact RFC 4072S User Manual

Phoenix Contact RFC 4072S
272 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #38 background imageLoading...
Page #38 background image
RFC 4072S
38 / 272
PHOENIX CONTACT 108580_en_02
2.3.3 Determining F_WD_Time IN/F_WD_Time OUT to be param-
eterized and checking/validating that the safety function
can be implemented
Having calculated the upper and lower limits of the F_WD_TimeIN/F_WD_TimeOUT as
described in the two previous sections, you now need to determine the F_WD_Ti-
meIN/F_WD_TimeOUT watchdog times that are to be parameterized within these limits for
the safety function that is to be implemented. You then need to check/validate that the
required safety function can be implemented using the determined values.
The values are essentially determined as follows:
The relationship between the values for F_WD_Time IN and F_WD_Time OUT is based on
the relationship for the minimum F_WD_Time and the system availability determined in Sec-
tion 2.3.2 on page 32.
Example Based on the maximum possible safety function response time, the following requirement
must be met:
The watchdog times to be parameterized are chosen as follows in the example:
Factor 2 has been chosen here so that it is still possible to later increase the PROFINET
repeat cycles by the monitor factor or the PROFINET update time without endangering sys-
tem availability by exceeding the F_WD_Time monitoring time.
As a result, the values selected in the example project (see Figure 4-46 on page 123 and
Figure 4-47 on page 124) described in Section 4.3.1 are within the permissible range:
 Sum of the watchdog times is less than 200 ms.
(F_WD_Time IN
min
+ F_WD_Time OUT
min
) < (F_WD_Time IN + F_WD_Time OUT) < (F_WD_Time IN
max
+ F_WD_Time OUT
max
)
F_WD_Time IN
max
+F_WD_TimeOUT
max
=200ms (Upper limit from the safety
function)
F_WD_Time OUT
min
=24.5ms (From the example in
Section 2.3.2)
F_WD_Time IN
min
=50ms (Assumed for the example
calculation)
F_WD_Time OUT ≈ 2x24.5ms  F_WD_Time OUT = 50 ms
F_WD_Time IN = 2 x 50 ms = 100 ms
Minimum F_WD_Time (IN+OUT) < F_WD_Time (IN+OUT) to be parameterized < Maximum F_WD_Time (IN+OUT)
(50 + 24.5) ms
< (100 + 50) ms < 200 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact RFC 4072S and is the answer not in the manual?

Phoenix Contact RFC 4072S Specifications

General IconGeneral
BrandPhoenix Contact
ModelRFC 4072S
CategoryController
LanguageEnglish

Related product manuals