Function description
Operating Manual PNOZ s30
1001715-EN-19
| 19
} Automatic start
– Position monitoring is started when a rising edge has been detected at the start input.
– Position monitoring is started when the parameter set has been switched over and
position monitoring is used in the current parameter set.
– Position monitoring is restarted when the limit value has been exceeded and a rising
edge has been detected at the start input.
– Active position monitoring is not started again by another rising edge at the start in-
put.
– Active position monitoring is restarted if another parameter set is selected, which also
uses position monitoring. This also applies if position monitoring is used in a different
switch function.
– Active position monitoring is deactivated if another parameter set is selected, which
does not use this position monitoring.
t
0
t
1
t
2
t
3
t
4
x
0
s [inc]
t
Pos. Monitoring
Lpos
Fig.: Sequence of position monitoring with automatic start
Legend
x
0
Reference position
L
pos
Position window
t
0
Device on
t
1
Start of position monitoring by selecting a parameter set via the Select inputs
t
2
Position monitoring is restarted by selecting a different parameter set
t
3
Position leaves the position window, assigned outputs will switch off
t
4
Restart of position monitoring by rising edge at the start input (S34)
Please note:
} Position monitoring cannot be used if proximity switches are employed.
} Managing the start type of the outputs is independent of the start type of the position
monitoring.
} In the event of an open circuit, position monitoring is automatically deactivated