Function description
Operating Manual PNOZ s30
1001715-EN-19
| 19
} Automatic start
Position monitoring is started when a rising edge has been detected at the start input.
Position monitoring is started when the parameter set has been switched over and
position monitoring is used in the current parameter set.
Position monitoring is restarted when the limit value has been exceeded and a rising
edge has been detected at the start input.
Active position monitoring is not started again by another rising edge at the start in-
put.
Active position monitoring is restarted if another parameter set is selected, which also
uses position monitoring. This also applies if position monitoring is used in a different
switch function.
Active position monitoring is deactivated if another parameter set is selected, which
does not use this position monitoring.
t
0
t
1
t
2
t
3
t
4
x
0
s [inc]
t
Pos. Monitoring
Lpos
Fig.: Sequence of position monitoring with automatic start
Legend
x
0
Reference position
L
pos
Position window
t
0
Device on
t
1
Start of position monitoring by selecting a parameter set via the Select inputs
t
2
Position monitoring is restarted by selecting a different parameter set
t
3
Position leaves the position window, assigned outputs will switch off
t
4
Restart of position monitoring by rising edge at the start input (S34)
Please note:
} Position monitoring cannot be used if proximity switches are employed.
} Managing the start type of the outputs is independent of the start type of the position
monitoring.
} In the event of an open circuit, position monitoring is automatically deactivated