PNOZ X10
Operating Manual PNOZ X10
19554-EN-09
| 18
Relay outputs 774700 774701 774703
External contact fuse pro-
tection, safety contacts
In accordance with the
standard EN 60947-5-1 EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24V
AC/DC, characteristic
B/C 6 A 6 A 6 A
External contact fuse pro-
tection, auxiliary contacts
Max. melting integral 240 A²s 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A 10 A
Blow-out fuse, slow 6 A 6 A 6 A
Blow-out fuse, gG 10 A 10 A 10 A
Circuit breaker 24 V
AC/DC, characteristic
B/C 6 A 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal
current while loading
several contacts
774700 774701 774703
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current
with 1 contact 8 A 8 A 8 A
Conv. therm. current
with 2 contacts 7 A 7 A 7 A
Conv. therm. current
with 3 contacts 5,6 A 5,6 A 5,6 A
Conv. therm. current
with 4 contacts 4,9 A 4,9 A 4,9 A
Conv. therm. current
with 5 contacts 4,4 A 4,4 A 4,4 A
Conv. therm. current
with 6 contacts 4 A 4 A 4 A