PNOZ X10
Operating Manual PNOZ X10
19554-EN-09
| 9
Type: DC
} U
B
: 24 VDC; Order no. 774709
Y1 Y2
A1 A2
S34S33
S22
Y3
S21S12S11
S12S11
S37
14 24 34 44 54 7264 82 92 02
13 23 33 43 53 7163 81 91 01
*Insulation between the non-marked area and the relay contacts: Basic insulation (over-
voltage category III), Protective separation (overvoltage category II)
Function Description
The safety relay PNOZ X10 provides a safety-oriented interruption of a safety circuit. When
supply voltage is supplied the "POWER" LED is lit. The unit is ready for operation when the
feedback loop Y1-Y2 and the start circuit S12-S34 are closed.
} Input circuit is closed (e.g. E-STOP pushbutton is not operated):
The LEDs "CH.1" and "CH.2" are lit.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54 and 63-64 are closed, auxiliary
contacts 71-72, 81-82, 91-92 and 01-02 are opened. The unit is active.
} Input circuit is opened (e.g. E-STOP pushbutton operated):
The LEDs "CH.1" and "CH.2" go out.
Safety contacts 13-14, 23-24, 33-34, 43-44, 53-54 and 63-64 are opened redund-
antly, auxiliary contacts 71-72, 81-82, 91-92 and 01-02 are closed.
Operating modes
} Single-channel operation: No redundancy in the input circuit, earth faults in the start and
input circuit are detected.
} Dual-channel operation with detection of shorts across contacts: Redundant input circuit,
PNOZ X10 detects
earth faults in the start and input circuit,
short circuits in the input circuit,
shorts across contacts in the input circuit.
} Dual-channel operation without detection of shorts across contacts: Redundant input cir-
cuit, detects PNOZ X10
earth faults in the start and input circuit,
short circuits in the input circuit.
} Automatic start: Unit is active once the input circuit has been closed.
} Manual start: Unit is active once the input circuit and the start circuit are closed.