| 24
Relay outputs 774538 774610
Utilisation category in accordance
with UL
Voltage 240 V AC G. P. 240 V AC G. P.
With current 8 A 8 A
Voltage 24 V DC Resistive 24 V DC Resistive
With current 5 A 5 A
Pilot Duty C300, R300 C300, R300
External contact fuse protection,
safety contacts
In accordance with the standard EN 60947-5-1 EN 60947-5-1
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24V AC/DC,
characteristic B/C 6 A 6 A
External contact fuse protection,
delayed safety contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 6 A
External contact fuse protection,
auxiliary contacts
Max. melting integral 240 A²s 240 A²s
Blow-out fuse, quick 10 A 10 A
Blow-out fuse, slow 6 A 6 A
Blow-out fuse, gG 10 A 10 A
Circuit breaker 24 V AC/DC,
characteristic B/C 6 A 6 A
Contact material AgSnO2 + 0,2 µm Au AgSnO2 + 0,2 µm Au
Conventional thermal current
while loading several contacts
774538 774610
Ith per contact at UB AC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact – 8 A
Conv. therm. current with 2 con-
tacts – 7,8 A
Conv. therm. current with 3 con-
tacts – 6,5 A
Conv. therm. current with 4 con-
tacts – 5,5 A
Conv. therm. current with 5 con-
tacts – 5 A