Conventional thermal current
while loading several contacts
774538 774610
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 7,8 A 7,8 A
Conv. therm. current with 3 con-
tacts 6,5 A 6,5 A
Conv. therm. current with 4 con-
tacts 5,5 A 5,5 A
Conv. therm. current with 5 con-
tacts 5 A 5 A
Times 774538 774610
Switch-on delay
With automatic start typ. 400 ms 400 ms
With automatic start max. 850 ms 550 ms
With automatic start after power
on typ. 400 ms 750 ms
With automatic start after power
on max. 870 ms 1.050 ms
With monitored start typ. 40 ms 35 ms
With monitored start max. 70 ms 60 ms
Delay-on de-energisation
With E-STOP typ. 15 ms 15 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 110 ms –
With power failure max. 150 ms –
With power failure typ. UB 240 V – 900 ms
With power failure max. UB 240
V – 1400 ms
With power failure typ. UB 24 V – 120 ms
With power failure max. UB 24 V – 170 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms +tv 50 ms +tv
After power failure 200 ms –
After power failure on wide-
range power supply – 1450 ms
Delay time tv 0,3 s, 5 s, 10 s, 20 s, 40 s, 60 s,
80 s, 100 s, 150 s, 200 s, 250 s,
300 s
0,1 s, 0,5 s, 1 s, 2 s, 4 s, 6 s, 8 s,
10 s, 15 s, 20 s, 25 s, 30 s
Time accuracy -15 %/+15 % +50 ms -15 %/+15 % +50 ms
Repetition accuracy 2 % 2 %
Waiting period with a monitored
start 300 ms 300 ms
Min. start pulse duration with a
monitored start 30 ms 30 ms