Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 42
5.10 Distance from walls
The edges of the safety zone must have a distance of 40 mm to walls or fixed objects on all
sides.
With this value, the function of the safety laser scanner is ensured. Depending on the re-
flective conditions of the walls or objects, higher allowances may be necessary (see Dis-
tance to intense light sources and to reflective surfaces [ 40]).
INFORMATION
Used value of the teach-in function for the distance to the walls
The PSENscan Configurator teach-in function uses a value of 100mm.
5.11 Planning of safety and warning zones and zone sets
} Specify the location and the size of the safety zone and the warning zone in accordance
with the safety assessment.
} Specify in what situations the switching operation of the zone sets are to take place.
5.12 Switchover time with zone selection
The zone selection is done by digital signals that are controlled by the control system. For
the changeover process a maximum switchover time (input delay in PSENscanConfigur-
ator) is defined. For this time, non-permitted signals may be present at the entrances to the
zone selection. After the switchover time has elapsed, a valid code for a zone must be
present at the inputs for zone selection. The switchover time can be adjusted in increments
of 30 ms, and it must be adapted to the performance of the control system.
Select the time where the control system can switch an input in a defined way.
5.13 Encoder
} Deviation from rated speed
The minimum value is 0%, the maximum value is 45%, 25% is preset
Formula for the max. permitted deviation in an application
Encoder Δ = ((V
max
– V
min
)/ V
min
) * 100
Exceeding the configured encoder Δ during operation is permitted only under specific
conditions.
When the configured encoder Δ is exceeded outside these conditions, the OSSDs
switch to the safe condition.
Conditions for permitted exceeding of the configured encoder Δ
Determined speed is in the range of -10cm/s to 10cm/s
Determined speed is in the range of -30 cm/s to -10 cm/s or in the range of 10cm/s to
30cm/s: Exceeding is permitted for max. 60s
The determined speed is ≤-30cm/s or ≥30cm/s: Exceeding is permitted for max.
20s