Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 49
5.15.3 Muting in one direction
DANGER!
Loss of the safety function when L muting is applied incorrectly.
Use L muting only to remove material from the danger zone.
} The muting status occurs
When the signal at the muting input 2 switches to High after the muting input 1 has
also switched to high (or the muting input 1 switches to High after the muting input 2)
and
The delay between the two signal changes is in the configurable area Muting activa-
tion delay [ms]. The max. delay can be configured between 1 and 16 seconds.
} The muting state is ended
When the configured time is reached or
after a multiple of the delay between the activation of the two muting sensors.
The Factor activation delay can be selected between 2 and 16.
Input
Muting 1
Input
Muting 2
Muting
function
At
Off
At
Off
At
Off
t
t
1
t
3
t
2
Fig.: Timing diagram L muting
Legend
t
1
Delay between Muting 1 and Muting 2 (configurable from 1-16 s)
t
2
Duration of the muting state (max. up to the configurable time exceeded)
t
3
Internal delay before the ending of the muting state (max. 30 ms)