Project configuration
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 52
5.16 Override
The override function can be used for the three types according to the timing diagrams.
} Single-channel pulses
} Activation is edge-triggered
} Activation is signal-triggered (only when using the 17-pin connection)
The Override function can only be activated when the input signals are controlled in accord-
ance with the timing diagrams.
Protective zone
Status
Override
Single-channel
Pulse
On
Off
On
Off
24 V
0 V
t
2 s< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
< 1 s
Fig.: Timing diagram for override function single-channel pulses
t
t < 400 ms
Condition
Override
Override 1
Yes
No
24 V
0 V
Status
Override
On
Off
Override 2
24 V
0 V
Fig.: Timing diagram for override function edge-triggered