First commissioning
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 85
WARNING!
Loss of safety function due to a safety distance that is too low
Depending on the application, serious injury or death may result.
} Depending on the degree of dust filtering, it is necessary to consider an
allowance for calculating the safety distance when installing the safety
laser scanner near intense light sources or reflective surfaces into ac-
count (see Distance to intense light sources and to reflective
surfaces [ 40]).
When calculating the safety distance, ensure that the allowance is
considered depending on the dust filtering.
Ensure that the new safety distance fulfils the specifications of the
safety assessment.
14. Click on the arrow . The next window Configure zones is opened.
Create the zones using the symbols in the tool bar on the right-hand side.
15. Click on .
Specify at least 3 (max. 15) reference points. Specify a max. permitted tolerance for
each reference point. Tol - is the tolerance for the side that faces the safety laser scan-
ner, Tol + is the tolerance for the side that is facing away from the safety laser scanner.
16. In a safety laser scanner arrangement you can configure the detection capability and
the zones for each slave unit separately.
When configuring a safety laser scanner arrangement, configure the detection capabil-
ity and the zones separately for each slave unit.
Select the slave unit(s) you want to configure one after the other and configure the de-
tection capability, the zones and the reference outlines, as required.
17. Switch the display in the work window to a live image by clicking on .
Check the safety function of the safety laser scanner as indicated in
Inspection [ 94].
Each time the test piece enters into the safety zone, the OSSDs must switch to the OFF
state and the status of the OSSDs in the Monitoring work window must show the viola-
tion of the safety zone.
The OSSDs must switch to the OFF state each time the reference point changes bey-
ond the tolerance range, and the status of the OSSDs in the Monitoring work window
must show the changing of the reference points.
18. Select Download configuration to device, to transfer the configuration to the device.
Click Accept to activate the downloaded configuration in the connected device and re-
ject the existing configuration on the connected device.