EasyManua.ls Logo

Pilz PSEN sc ME 5.5 08-17 - Page 87

Pilz PSEN sc ME 5.5 08-17
131 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
First commissioning
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 87
For Alarm 2 select Activated and select an output for the alarm.
With ALARM 1 an alarm is output when the front screen of the safety laser scanner is
dirty (CLEANW1 is shown on the display of the safety laser scanner).
With ALARM 2 an alarm is output when a device error has occurred.
For the first OSSD pair, select: Muting = Activated and Override status = Activated.
Select an output for Override status.
5. Select Automatic Reset = Activated for this safety laser scanner when an error state
is detected and an automatic reset is to be performed.
6. Click on the arrow . The next window Configure zone sets is opened.
7. Select Zone set = 3. Enter the input delay.
The pins are automatically assigned to the zone sets by PSENscan Configurator. The
assignment can be changed manually.
Note when mapping manually: Zone sets where a 0 or 1 is entered for all the zone
switching, are not permitted.
Automatic coding using PSENscan Configurator
Click for automatic coding of zone sets
Click on the arrow . The next window Input configuration is opened.
8. In the first safety zone, for Restart select the value Manual and assign a pin to the
manual restart.
For Restart select the value Automatic in the second safety zone and define the re-
start time (min. 80ms).
Select for both safety zones whether EDM is to be activated. When EDM is activated, a
pin must be assigned to the EDM input.
In the first safety zone, select the settings for muting.
In the first safety zone select Override = Activated and Override mode = Edge.
Select 2 outputs for muting, and also for override and override mode.

Table of Contents

Related product manuals