First commissioning
Operating Manual PSEN sc ME 5.5 08-17
1005388-EN-01
| 87
For Alarm 2 select Activated and select an output for the alarm.
With ALARM 1 an alarm is output when the front screen of the safety laser scanner is
dirty (CLEANW1 is shown on the display of the safety laser scanner).
With ALARM 2 an alarm is output when a device error has occurred.
For the first OSSD pair, select: Muting = Activated and Override status = Activated.
Select an output for Override status.
5. Select Automatic Reset = Activated for this safety laser scanner when an error state
is detected and an automatic reset is to be performed.
6. Click on the arrow . The next window Configure zone sets is opened.
7. Select Zone set = 3. Enter the input delay.
The pins are automatically assigned to the zone sets by PSENscan Configurator. The
assignment can be changed manually.
Note when mapping manually: Zone sets where a 0 or 1 is entered for all the zone
switching, are not permitted.
Automatic coding using PSENscan Configurator
Click for automatic coding of zone sets
Click on the arrow . The next window Input configuration is opened.
8. In the first safety zone, for Restart select the value Manual and assign a pin to the
manual restart.
For Restart select the value Automatic in the second safety zone and define the re-
start time (min. 80ms).
Select for both safety zones whether EDM is to be activated. When EDM is activated, a
pin must be assigned to the EDM input.
In the first safety zone, select the settings for muting.
In the first safety zone select Override = Activated and Override mode = Edge.
Select 2 outputs for muting, and also for override and override mode.