3.5 TMPR1 and TMPR2
These inputs are used to monitor the control panel box, detector housings and
siren cases using tamper switches. This input can also be utilized for panic
buttons, temperature sensors with dry contact outputs and more.
Connect the tamper switch to the input, TMPR1 or TMPR2 and the ground (–).
A 10 kW EOL resistor at the terminal input on the PCB. The EOL provides a
short/disconnect indication since the tamper switches are of the NO type.
NOTE:
Default programming is that both TAMPER inputs are enabled and without
EOL. Refer to the “System Configuration” screen in order to change the
defaults (section 5.6).